vacuum circuit breakers vcb VS1(ZN63) 12kv /24kv 630a/1250a handart type
1.Determine the rated voltage
2. Determine breaking capacity
3. Determine the rated current
4. Determine the installation method (A: handcart type B: fixed type)
5. Determine installation size
Vacuum circuit breakers vcb VS1(ZN63) 12kv /24kv 630a/1250a handart type
Product overview
VS1 (ZN63A) - 12 indoor high voltage vacuum circuit breaker, three-phase ac 50 hz, rated voltage of 12 kv power system of indoor switchgear, as power equipment, industrial and mining enterprises, power protection and control unit. Apply to working in the rated electric demand flow frequent operation, or more open circuit short circuit current. The circuit breaker operating mechanism and circuit breaker unibody design of ontology. Either as a fixed installation unit, also can equipped with feed mechanism, form a handcart unit.
Using the environment conditions
Ambient air humidity: cap + 40 ° ℃, lower limit - 15 ° ℃ * height: < 1000 m (if need higher elevation, the rated insulation level increase) Amplitude: the earthquake intensity is not more than 8 degrees Air relative humidity, average no greater than 95%, on average no greater than 90% No fire and explosion danger, serious pollution, chemical corrosion and the site of violent vibration
Specification
Item
Description
Unit
Data
1
Rated voltage
KV
12
2
Max. voltage
KV
12
3
Rated current
A
630/1250/2000A4000
4
Rated short circuit breaking current
KA
20/25/31.5/40
5
Rated short circuit making current
KA
50/63/80/100
6
Rated peak withstand current
KA
50/63/80/100
7
4S Rated withstand current
KA
20/25/31.5/40
8
Rated insulation level
Power frequency voltage(when losing a circuit)
KV
Dreaker 42
Impulse withstand voltage(when losing a circuit)
Dreaker 75
9
Rated operating sequence
OC-0.3s-CO-180S-CO
10
Mechanical life
Times
20000
11
Rated short circuit current breaking time
Times
50
12
Rated close brake voltage of operating machnie
V
110,220
13
Rated break brake voltage of operating machnie
V
110,220
14
Contact stroke
mm
11±1
15
Exceed range(the compress length of contact sping)
mm
3.5±0.5
16
Different period of three-phase break and close break
ms
≤2
17
The jump time of contact close break
ms
≤2
18
Average break speed
m/s
0.9~1.2
19
Average closing speed
m/s
0.5~0.8
20
opening time
Ubder max.operating voltage
S
≤0.05
Under min.operating voltage
≤0.08
21
Closing time
s
0.1
22
Resistance of each phase main loop
μΩ
≤40
23
Contacts limit ersion
mm
3
Detailed Photos
Installation dimensions
Packing details
by strong wood box
OEM can be customized as required on the box.
Buy Guide
Determine the rated voltage
2. Determine breaking capacity
3. Determine the rated current
4. Determine the installation method (A: handcart type B: fixed type)
5. Determine installation size
About Us
Hebei Liebang Electric Technology Co. LTDwas established in 2000, located in Hebei, China, covering an area of 20,000 square meters, is a group integrating R&D, manufacturing, sales and service. Our products cover many fields such as transformers, switch cabinets, electricity meters, wires and cables, and are widely used in construction, energy, communication and other industries.The company has its own technology research and development team. All products can be individually designed according to structural, mechanical and electrical principles. With advanced production equipment, testing equipment, production line and computer network control system, it is a leading domestic power equipment manufacturer in terms of product production, component selection and assembly. It has also passed ISO9001, ISO14001, ISO45001, CQC, test report and other quality system certifications, and the credit rating AAA certificate.We sincerely invite you to visit our factory for guidance and negotiation, and to explore potential cooperation opportunities.